Silverflame Expansion Joint Test Data |
|
Test
Reference |
Test
Type |
Plane |
Gap Size
(mm) |
Seal
Outside Diammeter(mm) |
Wall
Width (mm) |
Integrity |
|
LPC CC85398 |
BS476 |
Vertical &
Horizontal |
5-10
11-20
21-30
31-40
41-50
51-60
61-70
71-80 |
20
26
36
57
69
83
97
104 |
2.5
3.5
3.5
5
5
5
5
5 |
120 min
120 min
120 min
120 min
120 min
120 min
120 min
120 min |
|
BTC5359 |
BS476 |
Vertical |
20
30
50
60 |
38
38
69
69 |
6
6
8
8 |
240 min
240 min
240 min
240 min |
|
LPC CC87369 |
BS476 |
Vertical &
Horizontal |
5 -10
11-20
21-30
31-40
41-50
51-60
61-70
71-80
5 -10
11-20
21-30
31-40
41-50
51-60
61-70
71-80 |
20
26
36
57
69
83
97
104
20
26
36
57
69
83
97
104 |
2.5
3.5
3.5
4
5
5
6
6
4
5
6
6
8
8
8
8 |
120 min
120 min
120 min
120 min
120 min
120 min
120 min
120 min
240 min
240 min
240 min
240 min
240 min
240 min
240 min
240 min |
|
Silvertown G5 |
40 year life
cycle & compression set test |
n/a |
n/a |
Silverflame
Quelfire
Promaseal
Nullifire |
suitable
unsuitable
unsuitable
unsuitable |
|
CDL 549 |
Comparison of
Fire Testing |
Horizontal |
20
30 |
Silverflame
Quelfire
Promaseal
Nullifire |
240 min
240 min
180 min
210 min |
|
Hann Tucker
7452/1 |
Acoustic
Testing |
Horizontal &
Vertical |
10
20
30
40
50
60
70
80 |
n/a |
41 dB
40 dB
40 dB
41 dB
40 dB
40 dB
39 dB
39 dB |
| |